Basement Smoke Exhaust Systems
(Design, Supply, Installation, Testing, Commissioning & AMC for Basement Smoke Exhaust & Car Park Smoke Extraction Systems)
(Design, Supply, Installation, Testing, Commissioning & AMC for Basement Smoke Exhaust & Car Park Smoke Extraction Systems)
Keep basement car parks and below-ground spaces safer with Basement Smoke Exhaust Systems from Compress India. We help project teams plan smoke extraction, fresh air supply, jet fan ventilation, controls and fire alarm integration around the basement layout and approved fire strategy.
Whether you are developing a residential tower, commercial complex, shopping mall, hotel or hospital with basement parking, contact Compress India for a project-specific assessment and quotation.

A dependable basement smoke exhaust system needs coordinated engineering from airflow calculations through fire-mode testing. Compress India provides a project delivery approach covering equipment selection, installation, commissioning and maintenance, with specialist CFD analysis and approval support defined to suit your scope.
Share your basement layouts, fire consultant’s requirements and project schedule to discuss a suitable solution.
What Is a Basement Smoke Exhaust System?
A basement smoke exhaust system removes smoke and hot gases from below-ground spaces such as car parks, service floors and storage areas. It typically combines high-temperature smoke exhaust fans, fresh air supply, ducts or jet fans, smoke dampers, detection and automatic controls.
Its purpose is to keep escape routes usable for the design period, support firefighting access and limit smoke spread to upper floors. The system forms part of the wider basement fire safety strategy alongside compartmentation, sprinklers, fire alarm and protected staircases.
Why Basements Need Dedicated Smoke Exhaust
Limited Natural Openings Below Ground
Most basements have few or no external openings, so smoke cannot vent naturally. Mechanical basement smoke extraction gives smoke and heat a controlled route to open air.
Rapid Smoke Logging Under Low Ceilings
Low ceilings leave little space for a smoke layer to form above occupants. Smoke can fill a basement car park quickly and reduce visibility along escape routes.
High Fire Load in Basement Car Parks
Parked vehicles, tyres, fuel and plastics create a substantial fire load. A single vehicle fire can produce large volumes of dense, toxic smoke.
Smoke Migration Through Ramps, Lifts & Staircases
Buoyant smoke rises through ramps, lift shafts and staircase openings towards occupied floors. Smoke exhaust works with lobbies, pressurisation and fire doors to restrict these paths.
Protecting Basement Escape Routes
Occupants must find exits across a large, often unfamiliar floor plate. Smoke exhaust supports evacuation by limiting smoke exposure around exit staircases and walkways.
Supporting Firefighting & Smoke Clearance
Firefighters must descend into a basement fire rather than approach it from outside. Controlled smoke exhaust can improve access, and smoke clearance helps restore visibility once the fire is under control.
Fire NOC & Building Code Compliance
Basement ventilation and smoke exhaust are routinely examined during fire approvals and inspections. Applicable requirements and acceptance conditions must be established with the project consultant and fire authority.
How a Basement Smoke Exhaust System Works
1. Fire Is Detected
Smoke detectors, heat detectors or sprinkler flow switches identify a fire condition. The fire alarm system sends the required signals according to the approved cause-and-effect matrix.
2. Normal Ventilation Switches to Fire Mode
Fans running in normal car park ventilation mode change to their designated fire-mode duty. Equipment that could spread smoke is stopped or isolated.
3. Smoke Exhaust Fans Start at Fire-Mode Duty
Exhaust fans run at the airflow required for smoke extraction, usually higher than normal ventilation duty. Damper positions, power availability and interlocks are confirmed through the control sequence.
4. Smoke Is Moved Towards Extraction Points
In ducted systems, high-level grilles draw smoke into exhaust ducts. In jet fan systems, ceiling-mounted jet fans push smoke towards dedicated exhaust shafts.
5. Fresh Air Enters Through Planned Paths
Replacement air enters through ramps, louvres, fresh air shafts or supply fans. Its route and velocity must support extraction without spreading smoke into clear areas.
6. Smoke Is Discharged Safely Outdoors
Exhaust shafts discharge smoke to open air at ground or roof level. Discharge points must stay clear of escape routes, building openings and fresh air intakes.
7. Smoke Dampers Open or Isolate Zones
Motorised dampers open extraction routes for the affected smoke zone and close paths that could spread smoke. Their positions follow the approved zoning logic.
8. Fire Alarm & Smoke Control Panels Coordinate the System
Panels manage fans, dampers, jet fans and status feedback, and provide manual override for firefighters. The precise sequence is project-specific; several of these steps may run at the same time.
Understanding Smoke Behaviour in Basements & Car Parks
Ceiling Jet & Horizontal Smoke Spread
Hot smoke rises to the ceiling and spreads sideways as a ceiling jet. In a large basement it can travel far from the fire before it descends.
Shallow Smoke Layers Under Low Ceilings
Basement ceiling heights leave only a shallow reservoir for smoke. The smoke layer can reach head height much faster than in taller spaces.
Effect of Beams, Downstands & Services
Deep beams, ducts and cable trays break up the ceiling and trap smoke in pockets. They also obstruct jet fan throw and affect detector coverage.
Smoke Cooling & Loss of Buoyancy
Smoke cools as it travels across concrete surfaces and mixes with air. Cooler smoke loses buoyancy, mixes downwards and becomes harder to channel.
Vehicle Fire Characteristics
Vehicle fires can grow quickly and spread between adjacent cars. Fire size and duration depend on vehicle type, parking density and sprinkler protection.
Multi-Level Basement Connections
Ramps and open connections between basement levels can carry smoke to other floors. Each level and compartment needs its own defined smoke exhaust arrangement.
Wind & Stack Effects at Ramps and Shafts
Wind at ramp entrances and temperature differences in shafts influence airflow. These effects can assist or oppose the intended smoke movement.
Types of Basement Smoke Exhaust Systems
Ducted Basement Smoke Extraction Systems
Exhaust ducts with high-level grilles run across the basement and connect to smoke exhaust fans. They suit basements where ceiling space allows duct routes and smoke must be drawn from specific zones.
Jet Fan (Impulse) Ventilation Systems
Ceiling-mounted jet fans generate thrust that moves air and smoke towards main exhaust shafts. These ductless systems save ceiling space and are widely used in basement car parks.
Induction & Low-Profile Jet Fans
Induction fans and low-profile jet fans suit basements with restricted headroom. Their thrust, throw and smoke-duty rating must match the design.
Natural Basement Ventilation
Perimeter vents, stallboard lights, pavement lights and open shafts can ventilate a basement where the layout allows. Effectiveness depends on opening area, distribution and wind exposure.
Hybrid Natural & Mechanical Systems
Natural openings can be combined with mechanical extraction for lower levels or deep floor plates. Both modes must be assessed so they do not work against each other.
Zoned Basement Smoke Exhaust Systems
Large basements are divided into smoke zones, each with its own extraction route. Detection identifies the affected zone and controls activate the matching fans and dampers.
Multi-Level Basement Smoke Management
Multi-level basements need a separate smoke outlet for each level and compartment. Shared fresh air intakes and connecting ramps require careful coordination.
Smoke Clearance vs Smoke Control Systems
Smoke clearance systems help remove smoke after a fire has been suppressed. Smoke control systems aim to keep defined areas clear during the fire and typically need engineered analysis such as CFD.
Ducted vs Jet Fan Basement Smoke Exhaust
Ducted Smoke Exhaust
Ducts draw smoke from defined points at high level across the basement. They need ceiling space and add pressure losses, but give direct control over extraction locations.
Jet Fan Ventilation
Jet fans move smoke horizontally towards exhaust shafts without large ducts. Layout, thrust and activation timing need careful engineering, usually supported by CFD.
Headroom & Ceiling Space Constraints
Ducts compete with beams, sprinkler pipes, cable trays and vehicle clearance. Jet fan systems often free up headroom in low basements.
Installation & Services Coordination
Ductwork needs extensive fabrication and supports across the ceiling. Jet fans need fewer routes but must have a clear throw path.
Normal-Mode Energy Use
Both systems can provide day-to-day car park ventilation at reduced speed. CO sensor control can cut running hours and energy use in normal mode.
When a Combined Approach Is Appropriate
Some basements use ducts in irregular zones and jet fans across open parking areas. The combined arrangement must be assessed as one system.
Normal Ventilation vs Fire Mode in Basement Car Parks
Normal-Mode Car Park Ventilation
Day-to-day basement ventilation removes vehicle exhaust, heat and odours. For this mode, see our Car Park Ventilation Systems.
Fire-Mode Smoke Exhaust
In a fire, the system changes to its smoke exhaust duty, usually at a higher airflow. Fan ratings, dampers, power supply and controls must all support this emergency duty.
CO Monitoring & Demand-Controlled Ventilation
CO sensors adjust fan speed to measured pollution levels during normal operation. A fire alarm signal must always override CO-based control.
CO & NO₂ Sensor Placement
Sensors are placed along parking aisles, ramps and pedestrian routes at the heights set by the design and manufacturer. Coverage should reflect traffic patterns and potential dead zones.
Two-Speed & VFD-Controlled Fans
Two-speed motors or VFDs let one set of fans serve both normal and fire modes. Fire-mode operation must stay consistent with the fan’s tested smoke rating.
Switching From Normal Mode to Fire Mode
The changeover must be automatic, fast and verified during commissioning. Fans, jet fans and dampers should not remain in normal-mode settings after a fire signal.
Fresh Air & Make-Up Air for Basement Smoke Exhaust
Why Fresh Air Is Required
Extracted smoke must be replaced by incoming air. Without enough replacement air, exhaust fans cannot deliver their design airflow and doors may become hard to open.
Natural Fresh Air Through Ramps & Openings
Vehicle ramps, louvres and perimeter openings can supply replacement air where accepted in the design. Their availability during a fire, including shutters and gates, must be confirmed.
Mechanical Fresh Air Supply Fans
Supply fans deliver fresh air through dedicated shafts where natural paths are insufficient. Their fire-mode operation must follow the approved strategy and the applicable NBC interlock provisions.
Fresh Air Shaft Location & Separation
Fresh air intakes must be separated from smoke exhaust discharge points so smoke is not drawn back in. Location should also consider adjoining buildings and prevailing wind.
Supply Air Velocity & Distribution
High-velocity inlets can stir up smoke and push it towards escape routes. Distributed inlets with controlled velocity help maintain the intended airflow pattern.
Balancing Exhaust & Fresh Air
Balancing considers exhaust mass flow, smoke temperature, ramp openings and leakage. Supply should support extraction without pressurising the fire zone.
Preventing Smoke Recirculation
Exhaust discharge, fresh air intakes and openings at ground level must be coordinated. Recirculated smoke can contaminate clear zones and adjoining spaces.
Basement Smoke Exhaust Design Criteria
Basement Area, Height & Volume
Floor area, clear height and volume set the basic design envelope. Ramps, mezzanines and connected areas must be included where they share the smoke zone.
Number of Basement Levels
Each level adds smoke paths, shaft requirements and fresh air demand. Lower levels typically depend entirely on mechanical extraction.
Basement Use & Occupancy
Car parking, plant rooms, storage and retail uses carry different fire loads and risks. Mixed-use basements need each area assessed separately.
Fire Compartments & Smoke Zones
Compartment and smoke zone sizes decide how many extraction routes are needed. Zones should align with fire alarm zoning and sprinkler coverage.
Clear Headroom & Vehicle Clearance
Fans, ducts and dampers must fit within the ceiling zone without reducing the required vehicle headroom. Early coordination with the structural layout avoids clashes.
Beam Layout & Structural Obstructions
Beam depth and direction affect smoke movement, duct routes and jet fan throw. The layout should work with the structure rather than against it.
Exit Staircase & Lift Lobby Locations
Extraction should draw smoke away from exits and protected lobbies. Escape route positions strongly influence jet fan direction and exhaust locations.
Ramp & Opening Locations
Ramps often act as fresh air inlets and sometimes as smoke paths. Their position shapes airflow patterns across the basement.
Sprinkler Protection
Sprinklers limit fire growth but do not stop smoke production. Suppression assumptions must be agreed before the design fire is selected.
Firefighting Access Routes
Fire service access points, staircases and hose routes should remain usable. Some smoke control strategies aim to keep an approach path clear for firefighters.
Design Fire & Fire Scenario Analysis
Selecting the Design Fire
The design fire reflects vehicle types, parking arrangement and sprinkler protection. Assumptions should be documented and agreed before detailed calculations.
Single Vehicle Fire Scenario
A single car fire is a common starting scenario for basement car park design. Its growth rate and peak heat release influence smoke production and temperature.
Fire Spread Between Vehicles
Closely parked vehicles and car stackers can let fire spread from car to car. This increases fire size and duration beyond a single-vehicle event.
Electric Vehicle (EV) Fire Considerations
Battery fires can burn longer, re-ignite and release different toxic gases. Projects adding EV charging in basements should review the design fire, detection and firefighting access.
Fire Location Relative to Exits & Extract Points
Fires near exits, ramps or exhaust shafts behave differently from fires in the middle of a zone. Several locations should be assessed to find the governing case.
Sprinklered vs Unsprinklered Conditions
Sprinkler operation cools smoke and limits fire growth, but it also reduces smoke buoyancy. The design must account for the agreed suppression performance.
Basement Smoke Exhaust Rate Calculation
Air Changes per Hour (ACH) Method
Where the applicable provision specifies air changes, airflow is calculated from volume: airflow in m³/h = basement volume in m³ × ACH. For example, a 4,000 m² level with 3.0 m clear height holds 12,000 m³; at an approved 30 ACH, the exhaust duty is 3,60,000 m³/h (roughly 2,12,000 CFM).
Calculating Basement Volume
Volume is normally based on the floor area and clear height of each smoke zone or level. Treatment of ramps, plant rooms and connected areas must follow the design basis.
Normal-Mode vs Fire-Mode Airflow
Normal ventilation and fire-mode smoke exhaust use different air-change rates. Fan selection must cover both duties where one system serves both.
Jet Fan Thrust Calculation
Jet fan quantity is based on the thrust needed to move air across the zone towards exhaust points. Beams, walls and nearby surfaces reduce effective thrust.
Fresh Air Calculation
Fresh air quantity is set to support the exhaust duty through ramps, shafts or supply fans. Inlet velocity and pressure loss across openings must be checked.
Temperature & Density Correction
Hot smoke occupies more volume than ambient air. Calculations must distinguish smoke volumes at design temperature from fan duty at ambient conditions.
Pressure Loss Calculation
Shafts, ducts, dampers, grilles and discharge louvres all add resistance. Underestimated losses leave a correctly rated fan short of the required airflow.
Diversity & Safety Margins
Smoke exhaust fans serving the fire zone must deliver full duty at the same time. Normal HVAC diversity assumptions should not be applied to life-safety extraction.
Jet Fan Ventilation System Design for Basement Car Parks
Jet Fan Thrust & Throw
Each jet fan’s thrust and tested throw determine how far it can move air and smoke. Selection should rely on tested performance data, not nominal catalogue claims.
Jet Fan Spacing & Layout
Fans are spaced so their throw zones overlap and push smoke continuously towards exhaust shafts. Spacing is checked against each unit’s tested effective range.
Unidirectional vs Reversible Jet Fans
Unidirectional fans push air one way; reversible fans can change direction to suit the fire location. Reversible operation needs zone-based control logic.
Mounting Height & Clearance From Beams
Fans need clearance from beams, ducts and light fittings to develop their full throw. Mounting must also preserve vehicle headroom.
Activation Timing in Fire Mode
Some strategies delay jet fans in the fire zone so occupants can leave before smoke is mixed and moved. Timing is set by the approved strategy and verified during commissioning.
Jet Fan Control Zones
Jet fans are grouped into zones linked to their exhaust fans. Zone logic must stop jet fans from pushing smoke into unaffected areas.
Interlocks With Smoke Exhaust Fans
Jet fans are normally interlocked with their zone’s exhaust fans, because moving smoke without extraction only spreads it. Failure of an exhaust fan group must trigger the defined control response.
Avoiding Dead Zones & Recirculation
Corners, ramps and areas behind obstructions can trap smoke or polluted air. CFD analysis helps position additional fans or extract points.
CFD Analysis for Basement Car Park Smoke Exhaust
Why CFD Is Used for Basement Car Parks
CFD shows how smoke, heat and air move through complex basement geometry. It is commonly used to design and verify jet fan systems.
Fire Dynamics Simulator (FDS) & CFD Tools
FDS and other CFD tools model fire-driven flow and smoke transport. Results depend on input data, mesh resolution and competent interpretation.
Smoke Movement & Visibility Analysis
Simulation shows predicted smoke paths and visibility over time. It helps confirm that escape routes and exit approaches stay usable.
Temperature Analysis Near Exits & Access Routes
Temperature results identify heat exposure around exits, staircases and firefighting approaches. They also inform equipment temperature ratings.
CO Dispersion in Normal Mode
CFD can also check normal-mode CO dilution across parking aisles. This helps place jet fans and sensors for day-to-day ventilation.
Jet Fan Layout Optimisation
Modelling tests fan positions, directions and quantities against beams and obstructions. Revisions can remove dead zones before installation.
Multiple Fire Location Scenarios
A scenario set tests fires in different zones, near exits and near ramps. One favourable simulation does not prove performance for every credible fire.
Performance-Based Fire Engineering
CFD supports a documented engineering assessment reviewed by the fire consultant. Acceptance remains subject to the project’s approval process.
Basement Smoke Exhaust Fan Selection
High-Temperature Smoke Exhaust Fans
Smoke exhaust fans must be rated for the required temperature and operating duration. The installed arrangement must stay consistent with the fan’s test evidence.
Axial Smoke Exhaust Fans
Axial fans suit high-airflow basement extraction in shafts and plant rooms. Selection must account for system resistance and the required smoke-duty rating.
Centrifugal & Inline Smoke Exhaust Fans
Centrifugal and inline fans suit ducted systems with higher pressure losses. Motor protection, arrangement and certified operating conditions should be reviewed.
Smoke-Rated Jet Fans & Induction Fans
Jet and induction fans inside the smoke zone are exposed to hot smoke. They need a smoke-duty temperature rating suited to their location.
Fan Temperature & Time Rating
EN 12101-3 classes such as F200, F300 and F400 each pair a test temperature with a minimum operating time. The required class follows the applicable code, approved strategy and design exposure.
Dual-Purpose Fans for Ventilation & Smoke Exhaust
One fan set can provide normal car park ventilation and fire-mode smoke exhaust. Fire-mode speed control, bypass and protection settings must match the fan’s approved configuration.
Duty / Standby Fan Configuration
Where standby provision is required, controls must deliver the intended changeover. A spare fan alone does not address shared power or control failures.
Emergency Power Requirements
Smoke exhaust fans need an alternative power supply that keeps them running in a fire. Starting currents and simultaneous fire-system loads need electrical coordination.
Basement Smoke Exhaust Ductwork & Shafts
Smoke Exhaust Shafts in Masonry or RCC
Exhaust shafts are commonly built in brick masonry or RCC as part of the structure. Shaft enclosures must provide the fire resistance their function requires.
Separate Smoke Outlets for Each Level
In multi-level basements, each level and compartment needs its own smoke outlet duct or ducts. A shared intake duct may serve several levels where the design allows.
Fire-Rated Smoke Exhaust Ducts
Metal smoke exhaust ducts must suit their location, temperature and fire-resistance requirement. Construction, joints, supports and insulation form part of the assessed system.
Duct Routing Around Beams & Services
Routes must work around beams, sprinkler mains and cable trays without excessive bends. Every change in direction adds pressure loss.
Exhaust Grilles & Extract Points
Grilles are placed at high level within each smoke zone, where smoke collects. Spacing and face velocity affect extraction efficiency.
Discharge Location at Ground or Roof Level
Smoke discharge must be kept away from entrances, escape routes, windows and fresh air intakes. Ground-level outlets need protection from blockage and public access.
Duct Leakage Control
Leakage reduces effective extraction from the basement. Proper sealing and specified leakage tests help verify delivered airflow.
Fire-Rated Penetration Sealing
Wall and slab penetrations need compatible fire-stopping systems. Generic sealants should not be assumed suitable for every duct or shaft.
Access & Maintenance
Provide access to dampers, fans, sensors and inspection points. Concealed equipment without service access creates long-term problems.
Smoke Dampers & Fire Dampers in Basements
Motorised Smoke Dampers
Motorised dampers open and close smoke exhaust routes for each zone. Their classification, leakage performance and actuator duty must suit the smoke-control function.
Fire Dampers at Transformer & Electrical Areas
Fire dampers are needed where ventilation ducts cross transformer areas or electrical switchboards. Damper selection must not close a route that is required for smoke exhaust.
Zone Isolation Dampers
Isolation dampers direct extraction to the affected zone and level. Commanded positions must match the active fire scenario.
Fresh Air Dampers
These dampers open designated replacement air paths. Their free area and verified operation directly affect exhaust performance.
Damper Actuators & Position Feedback
Actuators must move dampers within the required time under fire conditions. Position feedback confirms the damper has actually moved.
Damper Fail-Safe Operation
The correct failure position depends on each damper’s role. Fail-open or fail-closed behaviour must follow the fire strategy, not a universal rule.
Main Components of a Basement Smoke Exhaust System
Smoke Exhaust Fans
High-temperature rated fans remove smoke at the specified airflow, pressure and temperature conditions.
Fresh Air Supply Fans
Supply fans deliver replacement air through dedicated shafts where natural paths are insufficient.
Jet Fans & Induction Fans
Ceiling-mounted thrust fans move smoke and polluted air towards exhaust shafts in ductless systems.
Smoke Exhaust Shafts & Ducts
Shafts and ducts carry smoke from each level and zone to safe discharge points.
Exhaust & Supply Grilles
Grilles and louvres form the extraction and replacement air openings within each zone.
Motorised Smoke Dampers
Dampers select, isolate or open smoke exhaust routes according to the approved sequence.
Smoke & Heat Detectors
Detection devices provide fire inputs suited to the basement’s height, layout and vehicle exhaust environment.
CO & NO₂ Sensors
Gas sensors control normal-mode ventilation and alert occupants to high pollution levels.
Smoke Control Panel
The panel coordinates fans, dampers and jet fans, shows system status and reports faults.
VFD & Starter Panels
Drives and starters control fan speed and starting, with fire-mode operation set to suit the fan’s approved configuration.
Fire Alarm Interface
The interface passes alarm, zone and control signals between detection and smoke exhaust systems.
Firefighter Override Controls
Dedicated controls let authorised responders start, stop or adjust the system, with clear status indication.
Emergency Power Supply
An alternative power source keeps smoke exhaust equipment running when normal power fails.
Fire-Rated Cables
Fire-resistant cables, supports and routing keep critical circuits working for the required duration.
Fire Detection & Sensors in Basement Car Parks
Smoke Detectors
Smoke detectors give early warning but can be affected by vehicle exhaust and dust. Detector type and placement must suit the car park environment.
Heat Detectors & Linear Heat Detection
Heat detectors and linear heat cables tolerate dirty air better than smoke detectors. They respond later, which the activation strategy must account for.
Sprinkler Flow Switch Inputs
Sprinkler flow switches can confirm a fire in a specific zone. Many basement strategies use them to trigger zone-based smoke exhaust.
CO Detection & Automatic Ventilation Start
CO detectors control normal-mode fan speed and raise alarms at high levels. Some fire NOC conditions also require CO detection to start mechanical ventilation automatically.
Detection Zoning Aligned With Smoke Zones
Detection zones should match smoke exhaust zones so the right fans and dampers respond. Mismatched zoning can start extraction in the wrong area.
Avoiding False Activation
Exhaust fumes, steam and dust can cause nuisance alarms in car parks. Suitable detector choice and confirmation logic, such as two-detector coincidence, reduce unwanted activations.
Controls & Fire Alarm Integration
Automatic Fire Mode Activation
The system switches to fire mode on agreed alarm inputs from detectors or sprinklers. A manual start arrangement must also be available.
Zone-Based Fan Activation
Controls start the exhaust fans, jet fans and dampers serving the affected zone. Unaffected zones respond as the strategy defines.
Exhaust Fan Sequencing
Dampers open before or as exhaust fans start, as designed. Fire-mode stopping and reset arrangements must also be defined.
Jet Fan Sequencing
Jet fans start, delay or reverse according to the fire zone and strategy. Their operation is linked to exhaust fan status.
Fresh Air Fan Sequencing
Supply fans start, stop or change duty as the approved strategy requires. NBC interlock provisions for supply fans must be reconciled with the make-up air design.
CO Control Override
A fire signal must override CO-based speed control and normal-mode schedules. The override should be proven during commissioning.
Cause & Effect Matrix
The matrix maps each fire input to fan, damper and alarm actions. It is the central reference for programming, commissioning and maintenance.
Fan & Damper Status Monitoring
Monitoring shows the commanded and actual status of fans and dampers. Motor-running indication alone may not prove the required airflow.
Fire Control Room Panel
Operating switches with zonal indication are typically located in the fire control room. Labelling should let responders identify zones and equipment status quickly.
BMS Integration
The BMS can monitor fans, CO levels and faults where included in the design. Life-safety control must stay independent of BMS failures.
Emergency Manual Override
Manual override allows authorised intervention during an incident. Its priority over automatic operation must be documented and tested.
Basement Smoke Exhaust Cause & Effect Sequence
Fire Detection
A detector, sprinkler flow switch or manual call point identifies the affected zone and starts the fire-mode sequence.
Normal Ventilation Overridden
Normal-mode schedules and CO control are overridden. Fans with no smoke-control role are stopped or isolated.
Smoke Damper Activation
Dampers open exhaust and fresh air paths for the affected zone and close routes that could spread smoke.
Smoke Exhaust Fan Activation
Exhaust fans run at fire-mode duty, with their status signals returned to the control panel.
Fresh Air Activation
Designated openings or supply fans provide replacement air in coordination with exhaust, as the approved strategy defines.
Jet Fan Activation
Jet fans in the relevant zones start in their programmed direction, immediately or after a set delay.
Staircase & Lift Lobby Pressurisation
Pressurisation systems for basement staircases and lift lobbies start with the fire alarm, where provided.
Alarm, Status & Firefighter Override
The panel displays operating and fault conditions, and authorised responders can take manual control. The final sequence must match the project-specific matrix.
Basement Smoke Exhaust & Building HVAC Integration
Normal Ventilation vs Fire Mode Operation
Car park ventilation and smoke exhaust serve different purposes. Equipment serving both needs clearly defined modes and suitable fire ratings.
Shutting Down AHUs & Other Ventilation
Air handling units, toilet exhausts and other systems that could spread smoke may need to stop or isolate in a fire. Units with a smoke-control role run in their defined fire mode.
Plant Rooms & Service Areas
Basement electrical rooms, DG rooms, pump rooms and STPs have their own ventilation needs. Their systems must be coordinated with the car park smoke exhaust strategy.
Preventing Smoke Recirculation
Return air paths, shafts and outdoor intakes must not carry basement smoke to other floors. Exhaust discharge should not contaminate fresh air intakes.
Fire & Smoke Damper Coordination
Damper actions must support compartmentation and the required extraction route at the same time. Conflicting commands can disable smoke removal.
Basement Smoke Exhaust & Staircase Pressurisation
Protecting Basement Staircases
Basement staircases are typically enclosed and entered through fire-resisting lobbies. Where pressurised, their performance must be checked with basement exhaust running and doors open.
Basement Lift Lobby Pressurisation
Where lifts serve the basement, the basement lift lobby is typically pressurised to keep smoke out. Pressure levels must not make doors difficult to open.
Smoke Check & Cut-Off Lobbies
Lobbies between the basement and staircases add separation from smoke-affected areas. Some fire NOC conditions require these lobbies to be mechanically pressurised.
Maintaining Building-Wide Pressure Balance
Basement exhaust can draw air from pressurised stairs and lobbies through open doors. Integrated assessment helps avoid lost pressurisation and airflow reversal.
Integrated Smoke Control Strategy
Treat basement exhaust, protected routes and connected shafts as one coordinated system. See our Staircase & Lobby Pressurisation Systems for the related interfaces.
Fire Safety Codes & Standards
NBC 2016 Part 4 – Basement Fire & Life Safety
NBC 2016 Part 4 is the key national reference for basement fire and life safety. Confirm the clauses, amendments and local adoption that apply to your project.
NBC 2016 Part 8 – Mechanical Ventilation
Part 8 covers mechanical ventilation, including normal-mode air changes. Use it alongside the Part 4 fire-mode provisions.
Maharashtra Fire Prevention & Life Safety Measures Act
For projects in Maharashtra, confirm the applicable Act, Rules, amendments and authority procedures. Statutory obligations and required certifications must be established for the property.
Local Fire NOC Conditions
Fire NOC conditions can specify basement air-change rates, CO detection interlocks and the location of ventilation controls. Review your NOC conditions before finalising the design.
BS 7346-7 – Smoke & Heat Control for Covered Car Parks
BS 7346-7 gives functional recommendations and calculation methods for car park smoke control, including impulse (jet fan) ventilation. It covers means of escape, firefighting support and smoke clearance objectives.
EN 12101-3 – Powered Smoke & Heat Exhaust Ventilators
EN 12101-3 covers the testing and classification of smoke exhaust fans. Specify the class required for each fan and its location.
NFPA 88A & NFPA 92
NFPA 88A addresses parking structures and NFPA 92 addresses smoke control systems. They may be used where adopted or accepted in the project basis.
Performance-Based Fire Engineering Requirements
A performance-based design needs agreed objectives, scenarios and acceptance criteria. Review responsibilities should be fixed before detailed analysis starts.
NBC Requirements for Basement Smoke Exhaust
The provisions below are those commonly applied from NBC basement requirements. Confirm the exact clause wording in the NBC edition and local rules adopted for your project.
Separate Ventilation for Each Basement
Each basement must be separately ventilated. Natural vents with an aggregate area of at least 2.5% of the floor area, spread evenly around the perimeter, are one accepted route.
Air Inlets & Smoke Outlets
Alternatively, air inlets at basement floor level and smoke outlets at ceiling level can be provided. Openings should be accessible to the fire brigade and marked “AIR INLET” or “SMOKE OUTLET”.
Separate Smoke Outlets in Multi-Level Basements
One intake duct may serve all basement levels, but each level and compartment needs its own smoke outlet duct or ducts. These ducts carry the same fire resistance rating as the compartment.
Mechanical Extraction for Lower Basements
Mechanical extractors are required for smoke venting from lower basement levels. They must operate with the detection and sprinkler systems, with an arrangement for manual start.
Extractor & Supply Fan Interlock
Extractors must keep running while supply fans stop automatically on fire detection. Designs relying on mechanical fresh air in fire mode must resolve this with the fire consultant and authority.
Fire-Mode Air Change Rate
The commonly applied NBC basement provision calls for mechanical extractors designed for 30 air changes per hour in a fire. Normal-mode rates follow NBC Part 8, and some NOC conditions set their own normal and fire-mode rates.
Alternative Power Supply
Mechanical extractors need an alternative source of electricity supply. The emergency supply must cover all designated smoke exhaust loads.
Ventilation Ducts & Fire Dampers
Ventilation ducts should be integrated with the structure in brick masonry or RCC as far as possible. Fire dampers are needed where ducts cross transformer areas or electrical switchboards.
Benefits of Basement Smoke Exhaust Systems
Keeps Escape Routes Clearer
A properly designed system limits smoke along exit routes for the design period. Occupants can locate staircases and exits more easily.
Limits Smoke Spread to Upper Floors
Extraction reduces smoke migration through ramps, lifts and staircases into occupied floors above.
Improves Visibility During Evacuation
Removing smoke helps occupants see exit signs and routes. Actual visibility depends on fire size, activation timing and system performance.
Reduces Heat Build-Up
Extracting hot gases limits heat accumulation beneath the basement slab. This supports tenable conditions and helps protect structure and equipment.
Supports Firefighter Access
Managed smoke conditions help firefighters locate and reach the fire. Smoke clearance after suppression speeds up post-fire operations.
Controls CO Levels in Normal Operation
Dual-purpose systems also ventilate the car park day to day. CO-based control keeps air quality within design limits.
Lowers Running Costs With Demand Control
Variable-speed fans driven by CO sensors run only as hard as needed. This reduces energy use compared with constant full-speed operation.
Supports Fire NOC Compliance
Documented design, installation and testing provide evidence for fire approvals. Compliance must be assessed against the project’s applicable requirements.
Where Basement Smoke Exhaust Systems Are Used
Residential Towers With Basement Parking
Multi-level basement car parks under residential towers need reliable smoke exhaust alongside everyday ventilation.
Commercial Office Buildings
Office basements combine parking with plant rooms and services, requiring coordinated zoning and extraction.
Shopping Malls & Retail Complexes
Mall basements handle heavy vehicle movement and may include retail or service areas below ground.
Hotels
Hotel basements combine guest parking, back-of-house areas and plant rooms that each need a suitable smoke strategy.
Hospitals
Hospital basements need smoke exhaust that supports the evacuation of occupants who may require assistance.
IT Parks & Business Centres
Large campus basements often span several buildings and need zoned smoke exhaust and CO control.
Mixed-Use Developments
Shared basements serving residential, retail and office users need a strategy that covers every use.
Metro, Railway & Transport Hubs
Underground concourses and parking linked to stations need coordinated smoke exhaust and evacuation routes.
Basement Plant Rooms & Service Areas
Electrical rooms, DG rooms, pump rooms and STPs below ground need ventilation and smoke management suited to their risks.
Basement Storage & Warehousing
Below-ground storage carries high fire loads and needs smoke exhaust sized to the stored goods and layout.
Basement Smoke Exhaust Installation Guide
Smoke Exhaust Fan Installation
Install fans in their approved orientation with suitable supports, connections and access. Installation details must preserve the fan’s smoke-duty classification.
Jet Fan Installation
Mount jet fans at the design positions, heights and directions with secure fixings. Check clearance from beams, light fittings and sprinkler pipes.
Duct & Shaft Installation
Follow the assessed duct construction, support and joint details. Confirm shaft dimensions, continuity and access before connecting equipment.
Smoke Damper Installation
Use the permitted installation arrangement and provide actuator access. Confirm identification, orientation and wiring against approved schedules.
Fresh Air System Installation
Install supply fans, louvres and openings without reducing their effective free area. Check for obstructions from shutters, grilles or security measures.
CO Sensor Installation
Mount sensors at the specified heights and locations with access for calibration. Keep them away from direct exhaust streams that could distort readings.
Fire Detection Installation
Position detectors according to the approved layout. Provide the access and environmental protection needed for maintenance.
Emergency Power & Fire-Rated Cabling
Install designated circuits with the specified fire-resistant cables, supports and routing. Coordinate emergency supply connections with the electrical design.
Smoke Control Panel Installation
Locate panels where authorised operation and maintenance are practical, such as the fire control room. Provide clear labelling and zone indication.
Fire Alarm Integration
Complete interfaces against the approved cause-and-effect matrix. Record signal definitions and verify end-to-end operation during commissioning.
Testing & Commissioning of Basement Smoke Exhaust Systems
Smoke Exhaust Airflow Measurement
Measure exhaust airflow with calibrated instruments at suitable points. Compare delivered airflow with the approved fire-mode duty.
Fan Performance Verification
Check rotation, speed, electrical readings, pressure and vibration. Confirm that fire-mode operation matches the fan’s approved configuration.
Jet Fan Direction & Operation Checks
Verify each jet fan’s direction, speed and zone response. Check that airflow moves towards the exhaust shafts as designed.
Fresh Air Measurement
Measure supply fan airflow and check natural inlet paths. Review inlet velocities that could disturb smoke movement.
Smoke Damper Functional Testing
Command each damper and verify physical movement and position feedback. Record response issues and obstructions.
CO Sensor Calibration & Control Testing
Calibrate sensors and test fan response at each control stage. Confirm that a fire signal overrides CO control.
Cause & Effect Testing
Test each fire input against its expected responses, zone by zone. Include defined faults, manual controls and reset arrangements.
Emergency Power Testing
Test the loss-of-normal-power scenario and changeover. Verify that smoke exhaust functions run on the emergency supply.
Integrated Fire-System Testing
Test smoke exhaust with fire alarm, sprinklers, pressurisation and HVAC shutdown together. The objective is to identify interface conflicts.
Fire NOC Witness Testing
Prepare for authority or consultant witnessing with agreed procedures and completed pre-checks. Record observations and close identified issues.
Testing & Commissioning Reports
Provide measured results, settings, test records and outstanding actions. These documents form the baseline for handover and AMC.
Smoke Testing for Basement Car Parks
Purpose of Smoke Testing
Smoke testing shows how the system moves visible smoke under controlled conditions. Its scope and limitations must be agreed before testing.
Cold Smoke Testing
Cold smoke shows airflow direction and dead zones but lacks the buoyancy of fire smoke. It is useful for checking jet fan airflow patterns.
Hot Smoke Testing
Hot smoke tests use a controlled heat source to create buoyant smoke. They give a closer picture of smoke behaviour than cold smoke alone.
Extraction & Airflow Verification
Observe whether smoke moves towards and leaves through the intended exhaust points. Use these observations alongside airflow measurements.
Fire Authority Witness Testing
Where witnessing is required, agree the method, precautions and acceptance observations in advance. Testing must be carried out by competent specialists.
Basement Smoke Exhaust Service, Maintenance & AMC
Scheduled Smoke Exhaust Fan Testing
Check fan condition, operation and status signals at the required intervals. Address bearing, belt and motor issues before they affect emergency readiness.
Jet Fan Inspection & Cleaning
Inspect jet fans for dust build-up, loose fixings and vibration. Dirty impellers and guards reduce thrust and throw.
Smoke Damper Testing
Exercise dampers and inspect actuators, linkages and feedback. A damper stuck in the wrong position can block the extraction route.
CO Sensor Calibration
Calibrate or replace CO sensors on the manufacturer’s schedule. Drifting sensors either waste energy or under-ventilate the car park.
Fire Alarm Interlock Testing
Recheck critical interfaces after maintenance, programming changes or alterations to the fire alarm system.
Control Panel Testing
Review indications, commands, fault reporting and control settings. Keep documentation aligned with the installed and programmed system.
Emergency Power Testing
Verify the standby supply and changeover functions within the approved maintenance schedule.
Duct & Shaft Inspection
Inspect accessible ducts and shafts for damage, leakage, debris and unauthorised alterations that could affect extraction.
Airflow Performance Testing
Compare measured airflow with commissioning records. Investigate significant drops rather than relying on motor operation alone.
Fire Audit & Compliance Support
Keep records of inspections, defects and corrective work for fire audits and NOC renewals. Discuss an AMC scope with Compress India that reflects your system and building obligations.
Common Basement Smoke Exhaust Problems & Solutions
Insufficient Smoke Exhaust Airflow
Check fan operation, duct resistance, leakage, damper positions and fresh air paths. Identify the restriction before proposing a larger fan.
Smoke Stagnating in Dead Zones
Corners, ramps and areas behind beams can trap smoke. Review jet fan layout and extract positions, using CFD where needed.
Jet Fans Pushing Smoke Towards Exits
Incorrect direction, zoning or sequencing can drive smoke into escape routes. Review the control logic against the approved strategy.
Smoke Entering Staircases or Lift Lobbies
Check pressurisation, door closers and lobby integrity alongside basement exhaust. Seal leakage paths and rebalance the system.
Inadequate Fresh Air
Blocked louvres, closed shutters or undersized openings restrict exhaust. Restore the designed inlet area or add mechanical supply.
High CO Levels in Normal Operation
Check sensor calibration, fan speed settings and jet fan coverage. Adjust control setpoints or add ventilation where dead zones exist.
Smoke Exhaust Fan Failure
Investigate the power supply, starter or VFD settings, controls and mechanical condition. Verify the standby response where one is provided.
Smoke Damper Failure
Inspect actuators, linkages, power and control signals. Free binding or obstructions and retest the full sequence.
Excessive Duct or Shaft Leakage
Locate the leakage and review construction details. Apply compatible repairs and repeat the airflow tests.
Fire Alarm Interface Failure
Trace the initiating signal through the interface and control logic. Verify wiring and programming through an integrated test.
Smoke Re-Entering Through Fresh Air Intakes
Exhaust discharge placed too close to intakes can recirculate smoke. Relocate discharge or intake points, or increase their separation.
Basement Smoke Exhaust Retrofit & Upgrades
Retrofitting Existing Basements
Start with a survey of installed equipment, layout and records. Compare the current system with the building’s approved fire strategy and NOC conditions.
Converting Ducted Systems to Jet Fan Systems
A jet fan conversion can free headroom and improve coverage. It needs a new design, CFD review and revised controls.
Increasing Smoke Exhaust Capacity
Added capacity needs review of shafts, fresh air, power and controls. A larger fan alone can create new problems.
Replacing Non-Rated Exhaust Fans
Replace fans that lack a suitable smoke-duty rating with correctly classified units. Confirm compatibility with the existing system resistance.
Adding CO Monitoring & Demand Control
CO sensors and VFDs can cut energy use in existing car parks. The fire-mode override must be retested after the upgrade.
Adding Mechanical Fresh Air
Mechanical supply can fix inadequate replacement air. Assess pressure effects and smoke movement before selecting equipment.
Smoke Damper & Control Panel Upgrades
Replace unreliable dampers and outdated panels with components suited to their smoke-control role. Retest every affected interface.
Planning for EV Charging Areas
New EV charging bays can change the basement fire risk. Review detection, smoke exhaust capacity and firefighting access before installation.
CFD Review of Existing Systems
A CFD study can assess an existing installation against agreed scenarios. Results depend on accurate survey inputs and engineering review.
Basement Smoke Exhaust System Cost in India
Basement smoke exhaust system pricing depends on the building and the required scope. A meaningful quotation needs more than floor area: levels, headroom, system type, controls and testing requirements all influence cost.
Cost by Basement Area & Number of Levels
Larger floor plates and more levels add fans, shafts and controls. Area alone is insufficient for reliable budgeting.
Smoke Exhaust Fan Cost
Fan cost varies with airflow, pressure, temperature-time rating, speed control and the required performance documentation.
Jet Fan System Cost
Jet fan quantity, thrust, smoke rating, control zoning and CFD requirements determine the jet fan budget.
Duct & Shaft Cost
Route length, duct dimensions, construction requirements, supports and site access influence ductwork and shaft costs.
Fresh Air System Cost
Costs depend on whether replacement air uses ramps, natural openings, supply fans or a combination, together with the associated controls.
CO Monitoring & Control Cost
Sensor quantity, panel features, VFDs and BMS integration influence control costs.
Fire Alarm & Control Integration Cost
Interface quantity, panel requirements, field wiring and programming complexity influence integration costs.
CFD & Fire Engineering Cost
Specialist analysis depends on basement size, scenario count, required outputs and review scope. Define deliverables before comparing proposals.
Testing & Commissioning Cost
Budget for airflow measurements, integrated testing, documentation and any specified smoke or witness testing.
Factors Affecting Total Project Cost
New-build versus retrofit conditions, working hours, access and approval requirements can materially affect the total. Share basement drawings with Compress India for an itemised quotation.
Basement Smoke Exhaust Systems in Mumbai, Navi Mumbai & Thane
Discuss Basement Smoke Exhaust Systems in Mumbai, Navi Mumbai and Thane with Compress India for new developments, operational buildings and retrofit projects. Your proposal can be scoped around site conditions, fire NOC conditions, consultant requirements and the available installation programme.
For a productive initial review, share basement plans and sections, parking layouts, the fire strategy and any existing equipment schedules. Confirm survey availability and the required design, installation or AMC scope with our team.
Why Choose Compress India for Basement Smoke Exhaust Systems?
Choose a project approach that addresses how fans, airflow and controls work together. Compress India focuses the discussion on your basement requirements, coordinated delivery and clear scope definition.
Smoke Control & HVAC Engineering Expertise
Coordinate smoke exhaust with car park ventilation and building services from the outset. This helps identify interfaces before installation begins.
Basement Smoke Exhaust Calculations
Request a proposal based on defined areas, levels, air-change rates and design assumptions. Clear calculations make equipment selection and technical review more straightforward.
Jet Fan & Ducted System Options
Compare ducted and jet fan options against your headroom, layout and budget. The chosen system should serve both fire mode and normal mode.
CFD-Based Smoke Control Design
Where specialist modelling is needed, discuss its scope, delivery arrangements and review requirements. Define the questions the study must answer before commissioning it.
Fire-Rated Equipment & Installation
Specify the required performance documentation and installation details. Component selection and site execution must support the same design intent.
Fresh Air & CO Control Integration
Address fresh air and CO-based ventilation alongside exhaust sizing. These interfaces are central to reliable basement performance.
Fire Alarm Cause & Effect Programming
Agree operating sequences, control priorities and fault responses before programming. A clear matrix supports efficient commissioning and future maintenance.
Testing, Commissioning & Fire NOC Support
Define measurable commissioning requirements and documentation deliverables. Approval support can be scoped around the consultant’s and authority’s stated requirements.
Retrofit & AMC Support
Discuss existing-system assessments, corrective work and maintenance coverage. A defined service plan helps preserve performance as the basement changes.
Get a Basement Smoke Exhaust Solution from Compress India
Plan your basement smoke exhaust requirements before ceiling services and shaft locations become fixed. Compress India can help you define the required scope and prepare a project-specific proposal.
Contact Compress India to request a design consultation, site assessment or quotation for Basement Smoke Exhaust Systems.
Connect with Our Smoke Control & HVAC Team
Share your project location, building use, number of basement levels, floor areas and current stage. Include whether you need a new installation, upgrade, commissioning support or AMC.
Basement Smoke Exhaust Design Consultation
Provide available architectural and structural drawings, fire consultant requirements, NOC conditions and equipment information. These inputs help establish the next engineering steps and quotation scope.
Related Smoke Management & Ventilation Solutions
Discuss atrium smoke extraction, staircase and lobby pressurisation, lift shaft pressurisation, car park ventilation and zoned smoke extraction as part of a coordinated building strategy. Explore our full range of Smoke Management Systems.

Atrium Smoke Extraction Systems
Learn More
Corridor Smoke Control Systems
Learn More
Mechanical Smoke Ventilation Systems
Learn More
Natural Smoke Ventilation Systems
Learn More
Zoned Smoke Extraction Systems
Learn MoreFrequently Asked Questions
Q1: What is a basement smoke exhaust system?
A basement smoke exhaust system removes smoke and hot gases from basement car parks and other below-ground spaces during a fire. It typically combines high-temperature exhaust fans, fresh air supply, ducts or jet fans, smoke dampers, detection and automatic controls.
Q2: Why is smoke exhaust required in a basement?
Basements have few openings, so smoke cannot vent naturally and quickly fills the space. Dedicated smoke exhaust helps keep escape routes usable, supports firefighters and limits smoke spread to upper floors.
Q3: How does a basement smoke exhaust system work?
Detection or sprinkler operation switches the system to fire mode. Exhaust fans extract smoke through ducts or shafts, jet fans move smoke towards extraction points where provided, and fresh air enters through planned paths.
Q4: What is the difference between basement ventilation and basement smoke exhaust?
Basement ventilation removes vehicle exhaust and CO during normal use. Smoke exhaust is the fire-mode duty, usually at a higher airflow, with high-temperature rated equipment, emergency power and fire alarm controls; one dual-purpose system often provides both.
Q5: How many air changes are required for basement smoke exhaust?
Commonly applied NBC basement provisions call for mechanical extractors designed for 30 air changes per hour in a fire, with normal-mode rates taken from NBC Part 8. Local fire NOC conditions can set their own rates, so the figures in your approved fire scheme govern.
Q6: How is basement smoke exhaust airflow calculated?
For an air-change-based design, airflow in m³/h = basement volume in m³ × the applicable ACH, calculated for each level or smoke zone. Jet fan systems also need thrust calculations, and complex basements may need CFD analysis.
Q7: What is a jet fan ventilation system?
A jet fan system uses ceiling-mounted fans that create thrust to push smoke and polluted air towards exhaust shafts. It avoids large ducts and is widely used in basement car parks with limited headroom.
Q8: Which is better for basement car parks: jet fans or ducted systems?
Neither suits every basement. Jet fans save ceiling space and suit open parking floors, while ducted systems give direct control over extraction points in irregular layouts; the choice depends on headroom, layout and the approved strategy.
Q9: Is fresh air required for basement smoke exhaust?
Yes. Extracted smoke must be replaced through ramps, openings, shafts or supply fans, or the exhaust fans cannot achieve their design airflow. Inlet locations and velocities must be planned so they do not spread smoke.
Q10: What temperature rating do basement smoke exhaust fans need?
Fans must be rated for the temperature and duration required by the applicable code and approved strategy. EN 12101-3 classes such as F200, F300 and F400 each pair a test temperature with a minimum operating time.
Q11: Can the same fans be used for normal ventilation and smoke exhaust?
Yes, dual-purpose fans are common in basement car parks. They must carry a suitable smoke-duty rating, run on emergency power in fire mode and have speed controls arranged to suit their approved configuration.
Q12: What is CO-based demand-controlled ventilation?
CO sensors measure carbon monoxide in the car park and adjust fan speed during normal operation. This saves energy while keeping air quality within limits, and a fire signal must always override it.
Q13: Do basement car parks need CFD analysis?
CFD is commonly used to design and verify jet fan systems and complex basements. It shows smoke movement, visibility and temperature for agreed fire scenarios, while acceptance remains with the fire consultant and authority.
Q14: How often should a basement smoke exhaust system be tested?
Testing frequency follows the applicable code, fire NOC conditions, manufacturer guidance and maintenance contract. Regular fan, damper, interlock and emergency power tests keep the system ready.
Q15: Does Compress India provide basement smoke exhaust systems in Mumbai, Navi Mumbai and Thane?
Yes. Compress India supports basement smoke exhaust projects across Mumbai, Navi Mumbai and Thane, from design and installation to testing, commissioning, retrofit and AMC. Share your drawings and project details to request a quotation.